SAUTER Building Information Modeling
How energy efficiency is improved
Efficient use in continuous control systems

Features
  • Continuous control of cold and hot water in closed circuits
  • Water quality as per VDI 2035
  • In combination with valve actuators AVM 322(S), AVM 234S and AVF 234S as control unit
  • Not suitable for steam, drinking water or potentially explosive atmospheres
  • Valve with flange connection as per EN 1092-2, seal form B
  • Regulating valve, free of silicone grease, painted black
  • Characteristic can be set with SUT (SAUTER Universal Technology) valve actuators to linear, equal-percentage or quadratic
  • The valve is closed when the spindle is moved out
  • Closing against the pressure
  • Valve body and seat made of grey cast iron
  • Stainless-steel spindle
  • Plugs made of stainless steel with metal-to-metal seal
  • Stuffing box made of stainless steel with wiper ring and double O-ring seal made of EPDM
1 - 3 of 3 | Results Per Page |   | Unit of Measure
1 

Part #

Nominal Pressure

Nominal Diameter

Connection Type

k_vs Value

CAD

RFA

Data Sheet

N/A VQD065F300 N/A PN 6 N/A DN 65 N/A Flanged N/A 63 m³/h N/A CAD Icon (for items table) N/A VQD
N/A Open
N/A VQD080F300 N/A PN 6 N/A DN 80 N/A Flanged N/A 100 m³/h N/A CAD Icon (for items table) N/A VQD
N/A Open
N/A VQD100F300 N/A PN 6 N/A DN 100 N/A Flanged N/A 160 m³/h N/A CAD Icon (for items table) N/A VQD
N/A Open
1 - 3 of 3 | Results Per Page |   | Unit of Measure