By continuing your navigation on this site, you accept the use of cookies in order to ensure the smooth running of your visit and to produce audience statistics.To find out moreI understand
SAUTER Building Information Modeling
Specially designed pressure limiter - DSL, DSH
ON/OFF Controllers
How energy efficiency is improved
Control and monitoring according to needs and with no auxiliary energy.
Features
Control and monitoring according to needs and with no auxiliary energy.
Features
- Switching point can be adjusted
- Sealable
- Pressure sensor made of brass for non-aggressive media (DSL)
- Pressure sensor made of stainless steel for aggressive media (DSH)
- Locking type: With falling pressure (DSL) or with rising pressure (DSH)
- SIL 2 certified as per EN 61508
- Approved for marine applications (GL and LR certified)
Part # |
Setting Range |
Min. Change for Reset |
Maximum Pressure |
Admissible Sensor Temperature |
CAD |
RFA |
Data Sheet |
---|---|---|---|---|---|---|---|
Part # N/A DSL140F001 | Setting Range N/A 0 to 2.5 bar | Min. Change for Reset N/A 0.4 bar | Maximum Pressure N/A 12 bar | Admissible Sensor Temperature N/A 70 ºC | CAD N/A | RFA N/A |
Data Sheet
N/A Open |
Part # N/A DSL143F001 | Setting Range N/A 0 to 6.0 bar | Min. Change for Reset N/A 0.5 bar | Maximum Pressure N/A 16 bar | Admissible Sensor Temperature N/A 70 ºC | CAD N/A | RFA N/A |
Data Sheet
N/A Open |
Part # N/A DSL152F001 | Setting Range N/A 6 to 16 bar | Min. Change for Reset N/A 1.2 bar | Maximum Pressure N/A 30 bar | Admissible Sensor Temperature N/A 70 ºC | CAD N/A | RFA N/A |
Data Sheet
N/A Open |
Part # N/A DSH127F001 | Setting Range N/A -1 to 5.0 bar | Min. Change for Reset N/A -0.4 bar | Maximum Pressure N/A 16 bar | Admissible Sensor Temperature N/A 110 ºC | CAD N/A | RFA N/A |
Data Sheet
N/A Open |
Part # N/A DSH143F001 | Setting Range N/A 0.5 to 6.0 bar | Min. Change for Reset N/A -0.45 bar | Maximum Pressure N/A 16 bar | Admissible Sensor Temperature N/A 110 ºC | CAD N/A | RFA N/A |
Data Sheet
N/A Open |
Part # N/A DSH146F001 | Setting Range N/A 1 to 10 bar | Min. Change for Reset N/A -0.8 bar | Maximum Pressure N/A 18 bar | Admissible Sensor Temperature N/A 110 ºC | CAD N/A | RFA N/A |
Data Sheet
N/A Open |
Part # N/A DSH152F001 | Setting Range N/A 2 to 16 bar | Min. Change for Reset N/A -1.5 bar | Maximum Pressure N/A 60 bar | Admissible Sensor Temperature N/A 110 ºC | CAD N/A | RFA N/A |
Data Sheet
N/A Open |
Part # N/A DSH158F001 | Setting Range N/A 5 to 25 bar | Min. Change for Reset N/A -1.8 bar | Maximum Pressure N/A 60 bar | Admissible Sensor Temperature N/A 110 ºC | CAD N/A | RFA N/A |
Data Sheet
N/A Open |
Part # N/A DSH170F001 | Setting Range N/A 15 to 40 bar | Min. Change for Reset N/A -2.0 bar | Maximum Pressure N/A 60 bar | Admissible Sensor Temperature N/A 110 ºC | CAD N/A | RFA N/A |
Data Sheet