How energy efficiency is improved
Allows demand-based volume flow control in order to optimise energy consumption in ventilation systems. Differential pressures of at least 1 Pa can be controlled to allow minimal volume flows at the lowest duct pressure and energy consumption.

Features
  • Controlling the return air in fume cupboards and controlling the supply and return air in laboratories, clean rooms, hospital wards and operating theatres using a VAV box or a damper and flow probe
  • Static measurement of differential pressure based on the capacitive method of measurement
  • Zero point can be calibrated using software
  • Adjustable end values of the differential pressure measuring range1)
    • 50...150 Pa
    • 100...300 Pa
  • Can be used for measuring in areas with dirty or contaminated return air
  • Brushless DC motor guarantees minimum energy consumption and a long service life
  • Electromechanical torque-based switch-off for safe operation
  • Extremely simple installation due to self-centring shaft adapter
  • Disengageable gear unit for manual adjustment and positioning of damper
  • Easy programming of the following applications using SAUTER CASE Components:2)
    • Volume flow control
    • Room pressure control
    • Duct pressure control
    • Flow control for fume cupboards
  • Efficient control algorithm for fast control loops
  • Integrated second control loop for:3)
    • Room-pressure control: can be ideally combined with EGP 100 with symmetrical measuring range
    • Fume-cupboard control ideally combined with SVU 100, SGU 100 and FCCP 200
  • 2 x RS-485 bus interface on RJ12 and connection terminal
    • Up to 31 subscribers in a segment with SLC (SAUTER Local Communication) protocol
    • Communication within network via BACnet MS/TP4)
    • Integration of EY-RU 3** digital room operating units
    • FCCP 200 display and alarm unit for fume-cupboard control or room monitoring
  • Input and output signals for integrating:
    • Setpoints and actual values
    • Analogue output
    • Priority control via switching contacts

    1) Available measuring ranges depending on hardware/type

2) Application support depending on hardware and software version in CASE VAV manual

3) Application support depending on hardware and software version in CASE VAV manual
VAV compact controller
Unit of Measure
1 

Part #

Power Supply

Torque

Positioning Time

Control Signal

Measuring Range Δp

CAD

RFA

Data Sheet

N/A ASV215BF152D N/A 24 V =/~ N/A 10 N·m N/A 3 to 15 s N/A 0..10V or bus N/A 0 to 150 Pa N/A CAD Icon (for items table) N/A Revit Icon (for items table) N/A Open
N/A ASV215BF152E N/A 24 V =/~ N/A 10 N·m N/A 3 to 15 s N/A 0..10V or bus N/A 0 to 300 Pa N/A CAD Icon (for items table) N/A Revit Icon (for items table) N/A Open