SAUTER Building Information Modeling
How energy efficiency is improved
Allows demand-based volume flow control in order to optimise energy consumption in ventilation systems. Differential pressures of at least 1 Pa can be controlled to allow minimal volume flows at the lowest duct pressure and energy consumption.

Features
  • Controlling the return air in fume cupboards and controlling the supply and return air in laboratories, clean rooms, hospital wards and operating theatres using a VAV box or a damper and flow probe
  • Static measurement of differential pressure based on the capacitive method of measurement
  • Zero point can be calibrated using software
  • Adjustable end values of the differential pressure measuring range1)
    • 50...150 Pa
    • 100...300 Pa
  • Can be used for measuring in areas with dirty or contaminated return air
  • Brushless DC motor guarantees minimum energy consumption and a long service life
  • Electromechanical torque-based switch-off for safe operation
  • Extremely simple installation due to self-centring shaft adapter
  • Disengageable gear unit for manual adjustment and positioning of damper
  • Easy programming of the following applications using SAUTER CASE Components:2)
    • Volume flow control
    • Room pressure control
    • Duct pressure control
    • Flow control for fume cupboards
  • Efficient control algorithm for fast control loops
  • Integrated second control loop for:3)
    • Room-pressure control: can be ideally combined with EGP 100 with symmetrical measuring range
    • Fume-cupboard control ideally combined with SVU 100, SGU 100 and FCCP 200
  • 2 x RS-485 bus interface on RJ12 and connection terminal
    • Up to 31 subscribers in a segment with SLC (SAUTER Local Communication) protocol
    • Communication within network via BACnet MS/TP4)
    • Integration of EY-RU 3** digital room operating units
    • FCCP 200 display and alarm unit for fume-cupboard control or room monitoring
  • Input and output signals for integrating:
    • Setpoints and actual values
    • Analogue output
    • Priority control via switching contacts

    1) Available measuring ranges depending on hardware/type

2) Application support depending on hardware and software version in CASE VAV manual

3) Application support depending on hardware and software version in CASE VAV manual
1 - 2 of 2 | Results Per Page |   | Unit of Measure
1 

Part #

Power Supply

Torque

Positioning Time

Control Signal

Measuring Range Δp

CAD

RFA

Data Sheet

Sort by
N/A ASV215BF152D N/A 24 V =/~ N/A 10 N·m N/A 3 to 15 s N/A 0..10V or bus N/A 0 to 150 Pa N/A CAD Icon (for items table) N/A Revit Icon (for items table) N/A Open
N/A ASV215BF152E N/A 24 V =/~ N/A 10 N·m N/A 3 to 15 s N/A 0..10V or bus N/A 0 to 300 Pa N/A CAD Icon (for items table) N/A Revit Icon (for items table) N/A Open
1 - 2 of 2 | Results Per Page |   | Unit of Measure
1